logo
about us our products contact us
¡¡¡¡ RODS¡¡ WINDING TUBES¡¡ COMPOSITE INSULATOR¡¡ CABLE ACCESSORIES¡¡ EPOXY
 

110kV cable ¡¡¡¡¡¡¡¡¡¡accessories

£­£­£­£­£­£­£­£­£­£­£­£­£­
66kV cable accessories
£­£­£­£­£­£­£­£­£­£­£­£­
35kV cable accessories
£­£­£­£­£­£­£­£­£­£­£­£­
10kV cable accessories
£­£­£­£­£­£­£­£­£­£­£­£­
Link boxes
£­£­£­£­£­£­£­£­£­£­£­£­£­
35kV indoor termination
35kV outdoor termination
35kV middle joint
SAMPLES

 

¡¡¡¡
¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡ô¡ô¡¡35kV cable accessories¡¡¡ô¡ô¡¡

¡¡¡ôCharacteristics of the products£º

¡¡¡¡¡ó We have adopted the advanced finite element method analysis software in the world to ¡¡carry on the optimization design the structure , parameter of In-door and out-door ¡¡termination for 10kV and 35kV, which made the inside , outside insulating axle , radial ¡¡electrical field distributing in ideal state
¡¡¡¡¡óThere is no lengthways parting line which Solve the problems form former product ¡¡structure like vertical parting line easy to pile up , absorb the dust , impurity to parting line ¡¡place when operating for a long time completely. the machinery , electric performance ¡¡become to worse where the place of products lengthways parting line, Especially in moist ¡¡state or rainy day. It is easy to form conductive throughout pass-ways along lengthways ¡¡parting line,which lead to the fact products is it hold in place with a net to flashover , ¡¡influence cable safety factor , circuit of normal running.
¡¡¡¡¡ó The product increases the pressure on the surface between silicone rubber terminations ¡¡and cable semiconductor shield.£¬improved the steady performance and seal waterproof ¡¡result of the products.
¡¡¡ô26/35kV Electrical performance index of the products:
¡¡¡¡1. AC voltage withstand: 117kV 5 min
¡¡¡¡2.AC voltage wet withstand: 104kV 1 min
¡¡¡¡3. RT partial discharge: 45kV¡Ü3pC £»
¡¡¡¡4. Constant load circling test: 3 periods, testing voltage: 65kV. Current through conductor; ¡¡heting:5h; cooling:3h; conductor highest temperature: 95¡æ~100¡æ.
¡¡¡¡5. High temperature partial discharge: 45kV¡Ü3pC, conductor highest temperature: ¡¡95¡æ~100¡æ £»
¡¡¡¡6. Lightning impulse voltage: 200kV(peak)¡À10 times, conductor highest temperature: ¡¡95¡æ~100¡æ
¡¡¡¡7. Humidity test:32.5kV,300h no flashover & electroetching £»
¡¡¡¡8. Salt fog test: 32.5kV,1000h no flashover & electroetching £»
¡¡¡¡9. Short circuit hot stability test:£º48.0kA,5s all parts no distortion £»
¡¡¡¡10. Short circuit stir stability test:£º1105.3kA,0.08s all parts no distortion £»

Copyright ©2005 Gphoenix. All rights reserved.